SOLICITATION NOTICE
J -- Replace Substation Alpha Relay B11912 Amendment 0002
- Notice Date
- 9/14/2026 12:00:00 AM
- Notice Type
- Solicitation
- NAICS
- 811310
— Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Contracting Office
- FA4661 7 CONS CD DYESS AFB TX 79607-1581 USA
- ZIP Code
- 79607-1581
- Solicitation Number
- FA466126R0010
- Response Due
- 9/18/2026 10:00:00 AM
- Archive Date
- 10/03/2026
- Point of Contact
- Robert Albrightson, Phone: 3253963864, Jesse T. Wisowaty, Phone: 3256966043
- E-Mail Address
-
robert.albrightson@us.af.mil, jesse.wisowaty@us.af.mil
(robert.albrightson@us.af.mil, jesse.wisowaty@us.af.mil)
- Small Business Set-Aside
- SBA Small Business Set Aside - Total
- Description
- The purpose of this amendment is to: 1. Attach the following documents related to contractor questions arising from the mandatory site visit: a) FA466126R0010 Q_A Final.pdf b) Dyess_AFB_Electrical_Study-Volume1 (Final Report)_Redacted.pdf c) Dyess_AFB, A-Sub Relay Settings.pdf d) Sub A Fdr A1 East Housing Relay.pdf e) Sub A Fdr A2 West Housing Relay.pdf 2. All other terms and conditions remain unchanged. This is a solicitation for the requirement of properly replacing the Substation Alpha Feeder Protection Relays at Building 11912 on Dyess AFB. The Contractor shall install (2) NEW GE 850 Feeder Protection Relays which are provided by the Government. The contractor shall install and wire in (2) new Feeder Protection Relays in accordance with NEC/ NETA standards. The Contractor shall program the (2) new Feeder protection relays to match programming of the previously installed GE 760 relays, via settings provided by the Electrical shop and test functionality without load. The Contractor shall coordinate with the Electrical shop prior to energizing the primary voltage for testing and commissioning. The Contractor shall commission and test the two new relays with full base load once installed with witnesses from Electrical, Contracting and R&O. The Contractor will coordinate with the Electrical Shop before conducting any power outages for acceptance tests if needed. Please see attachments for details.
- Web Link
-
SAM.gov Permalink
(https://sam.gov/workspace/contract/opp/4f509db3132e4b52b27d0744dd60ca39/view)
- Place of Performance
- Address: Dyess AFB, TX 79607, USA
- Zip Code: 79607
- Country: USA
- Zip Code: 79607
- Record
- SN07969254-F 20260916/260914230045 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |