SOLICITATION NOTICE
59 -- HLD Safety 480VAC Outlets
- Notice Date
- 6/7/2022 9:46:23 AM
- Notice Type
- Solicitation
- NAICS
- 335931
— Current-Carrying Wiring Device Manufacturing
- Contracting Office
- US ARMY ENGINEER DISTRICT WALLA WAL WALLA WALLA WA 99362-1876 USA
- ZIP Code
- 99362-1876
- Solicitation Number
- W912EF-22-Q-0159
- Response Due
- 6/21/2022 11:00:00 AM
- Archive Date
- 07/06/2022
- Point of Contact
- Amber Pope, Phone: 5095277223, Sara Edwards, Phone: 5095277216
- E-Mail Address
-
amber.r.pope@usace.army.mil, sara.edwards@usace.army.mil
(amber.r.pope@usace.army.mil, sara.edwards@usace.army.mil)
- Small Business Set-Aside
- SBA Total Small Business Set-Aside (FAR 19.5)
- Description
- TECHNICAL SPECIFICATIONS Safety Outlet Disconnect 1.0 Summary of Scope To furnish new 480VAC 30-amp safety outlets with a disconnect improve safety while working in the Powerhouse. These new safety outlets will benefit the project in the fact that ARC Flash Hazards will be greatly reduced by using new Safety items technology. These Outlets shall be supplied in accordance with the following specifications for the U.S. Army Corps of Engineers, Walla Walla District at Ice Harbor Lock and Dam, Burbank, Washington. The vendor shall supply new 480VAC 30-amp safety outlets with a disconnect, watertight locking plug ends, and must be delivered in new condition while meeting the requirements of the Buy American Act. . 2.0 Specifications 2.1 480VAC Safety disconnect outlet Voltage rating must be 600V RMS Dielectric strength must be able to withstand 1000V AC for 1 minute Must have certified interrupting rating of full rated current Must be 3 pole 4 wire receptacle The cord plug must not be able to be removed until the switch is turned off Must have a lockable RED handle that meets OSHA regulation for lockout tagout Must be pre-wired IEC pin and sleeve receptacle Housing must be NEMA type 4X, 12 and IP67 rated Must have mounting feet that are fully adjustable Mounting holes height must not exceed 11.5� center to center Mounting holes width must not exceed 7.5� center to center Mounting holes must be able to accept 5/16 diameter bolt All gaskets must be neoprene or Chloroprene Hubble HBL430MI7W or approved equal 2.2 480VAC Watertight locking plug Plug must be watertight IEC pin and Sleeve 3 pole 4 wire Voltage rating must be 600V RMS Dielectric strength must be able to withstand 3000V AC for 1 minute Must have certified interrupting rating of full rated current Plug must be IP67 rated gasket must be neoprene or Chloroprene must have a closure cap Must have cord clamp and locking ring Must have liquid tight adapters Housing must be RED in color Hubble HBL430P7W or approved equal 3.0 SCHEDULE All components shall be delivered no later than One hundred twenty (120) days after the receipt of contract award. Contractor shall make prior arrangements with the Government personnel at site to receive and unload the equipment. 4.0 Submittals and Requirements 4.1 Vendor Product Sheet and Drawings The vendor shall provide cut sheets with the dimensions, drawings, etc., with the quote for the Government to review for technical acceptability. All quoted information shall be sent to the Contracting Officer. All quotes shall be of sufficient in detail to show conformance to the specifications. Failure to provide acceptable proof of conformance or failure to meet the requirement of the specifications may result in disqualification 5.0 DELIVERY All items shall be delivered F.O.B. Destination to Ice Harbor Project. The contractor is responsible for packing and shipping components in a manner that will ensure undamaged and complete arrival to Ice Harbor Dam. Normal working hours at Ice Harbor Dam are 6:30 a.m. to 5:00 p.m., Monday through Thursday, excluding holidays. The delivery shall arrive between 7:00 a.m. and 3:00 p.m. during normal working days. Delivery made outside of this time slot will not be accepted. This is to allow for unloading and inspection. The delivery shall be made to the south side of the dam. The delivery address is as follows: Ice Harbor Dam 2763 Monument Drive Burbank, Washington 99323 Contractor shall make prior arrangements with the Government personnel at site to deliver and unload the equipment.
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/f0ec98a3c3f14ab1b67ba2e29374f77a/view)
- Place of Performance
- Address: Burbank, WA 99323, USA
- Zip Code: 99323
- Country: USA
- Zip Code: 99323
- Record
- SN06350278-F 20220609/220607230102 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |